Midwestern weather can be extreme and unpredictable. Whether your broken air conditioner is running up your bill or your aging furnace is banging at night, Lakes Heating & Air Conditioning has the expertise to keep your heating, cooling, and air quality systems working reliably.
Our licensed and insured technicians service all brands if your system needs repair, and we provide free estimates when you’re ready to install a replacement. Our new construction installations guarantee builders control from the design stage to the finished home. Offering solutions for Akron homes since 1974, you can trust both our experience and our upfront pricing.
Take control of your home comfort! Contact us to schedule installation and repair services in Akron today!

Emergency HVAC Repair
When minor problems become big, they cost more time and money. If you notice these signs, it’s time for immediate repair:
- Foul smells: Odors can indicate that you need a technician to clean and sanitize your air ducts.
- Reduced airflow: Lack of or no airflow may mean blocked air ducts or other ventilation problems.
- Leaks and water damage: A clogged drain line or uneven installation can lead to leaks from your cooling system.
- Loud knocking sounds: Odd noises often indicate that your system is nearing the end of its functionality.
Comprehensive Heating Services
With an average January low of around 20 degrees in Akron, you don’t want your heating system to break down on a freezing night. Whether you are installing a geothermal unit or radiant heating, or need repair work for your furnace, boiler, or heat pump, the Lakes Heating & Air Conditioning technicians have what you need to keep your home warm all winter. An efficient system also means lower energy bills, so you don’t have to choose between affordability and comfort.
Thorough Cooling Installation & Maintenance
Our team can promptly service your system so you can get back to your summer plans. Lakes Heating & Air Conditioning is here to repair your current system or replace it with a more energy-efficient one. Not every home has the exact cooling needs, and our ductless AC offers flexibility for your home’s unique layout. Our geothermal units work with renewable energy to significantly reduce your monthly bill.
Professional Indoor Air Quality Services
Is the tree pollen forecast high in Akron today? Even with the filters of an excellent heating and cooling system, your home is susceptible to mold, bacteria, and other particles that can impact your health and allergies. Air cleaners from Lakes Heating & Air Conditioning improve your air quality and peace of mind so you can breathe easier. Our humidifiers and dehumidifiers give you total control of your home’s comfort no matter what the weather’s like outside.
Why Trust Lakes Heating & Air Conditioning?
We know our community. Whether it’s meeting your heating, cooling, and air quality needs or sponsoring local scholarships and sports teams, Lakes Heating & Air Conditioning is a reputable family-operated part of Akron. Trust AACA-accredited service from our background-checked team. We’re here for our military, veteran, and senior neighbors with special discounts. Our technicians keep your HVAC system running while our upfront pricing and financing options keep your budget in mind.
Reach out to the Lakes Heating & Air Conditioning for your free estimate today!
Lakes Heating, Air Conditioning & Plumbing INC has completed 20 jobs in Akron, OH in June 2026. The most recent job was on June 9, 2026.Recent Jobs and Reviews in Akron, OH
Akron, OH at a glance
Job Locations and Reviews
Completed full HVAC system replacement including furnace and air conditioning unit. Installed new equipment with proper ductwork connections, ensuring all components were securely mounted and integrated with existing infrastructure including copper plumbing lines and PVC drainage systems. Verified blower assembly operation, tested all electrical connections, and confirmed system functionality upon completion.
Completed annual preventative maintenance on a seven-year-old Lennox air conditioning system. Performed comprehensive tune-up including system inspection, temperature and pressure readings verification, and operational testing of all components. Unit operating within normal parameters with no issues identified during service.
Responded to no hot water emergency call and provided installation estimate for customer-supplied 50-gallon gas water heater. Assessed existing basement utility room configuration including current water heater, plumbing connections, gas supply lines, venting requirements, and surrounding equipment including expansion tank and water treatment system. Evaluated copper supply piping, pressure relief valve placement, and drainage provisions. Documented existing installation with photographs showing water heater positioning against concrete block wall, overhead plumbing connections, and adjacent mechanical equipment. Provided comprehensive quote for complete water heater replacement including removal of old unit, installation of new 50-gallon gas water heater with proper venting, connection of hot and cold water lines, gas line hookup, installation of new temperature and pressure relief valve with proper drainage, and testing of all connections for leaks and proper operation.
Responded to service call for thermostat error message on Bryant Legacy rooftop package unit. Upon inspection, found heavily soiled air filters restricting airflow and causing system fault. Removed and replaced all four filters with clean units, restoring proper airflow and clearing thermostat service call indicator.
# Commercial Kitchen Floor Drain Cleaning and Maintenance
Responded to a clogged commercial kitchen floor drain system with standing water and visible debris accumulation. Upon arrival, assessed a rectangular drainage trough running through the center of white tile flooring, which contained discolored standing water with greenish-brown contamination and significant debris buildup.
Removed metal grating covering the drainage channel to access the obstruction. Cleared accumulated food waste, paper debris, and organic matter from both the grate surface and drain channel. Extracted blockage materials causing water backup in the trough system. Flushed the drain line to restore proper water flow and drainage capacity.
Cleaned the metal grate components and reinstalled them securely. Verified drainage system was flowing freely with no standing water remaining. Recommended regular maintenance schedule to prevent future buildup in this high-traffic commercial kitchen environment.
Completed comprehensive air conditioning tune-up on 26-year-old system. Performed inspection of indoor air handler unit located in attic space, checking electrical connections, condensate drainage, and airflow components. Inspected outdoor condenser unit, including fan motor assembly, refrigerant levels, and cleaned debris from base area. Utilized diagnostic equipment to verify system operation and performance parameters. Unit operational at time of service completion.
Responded to no cooling call on residential air conditioning system. Upon arrival, found system not operating. Inspected control board and verified proper thermostat operation showing system calling for cooling with indoor temperature at 78°F and setpoint at 76°F. Diagnosed failed control board in air handler unit. Replaced defective circuit board assembly and verified all wire connections to terminal blocks. Tested system operation and confirmed unit now cooling properly with thermostat displaying active cooling mode and normal humidity readings.
Completed full HVAC system retrofit in residential basement utility room, replacing existing furnace and air conditioning equipment with new Carrier-branded units. Installed new furnace, air handler, and associated ductwork connections to ceiling-mounted distribution system. All equipment positioned and secured on concrete floor with proper clearances maintained from existing water heater and utility systems. System tested and verified operational upon completion.
Conducted comprehensive estimate for complete HVAC system replacement, evaluating existing outdoor air conditioning condenser unit and indoor heating equipment. Assessed current system configuration, including electrical connections, condensate drainage, ductwork connections, and equipment placement to provide accurate replacement specifications and installation requirements for new furnace and air conditioning system.
Completed spring preventative maintenance on commercial HVAC system consisting of ground-level condenser units and rooftop package unit. Performed comprehensive inspection of all equipment, including visual assessment of condenser coils, fan operation, refrigerant line sets, and electrical disconnects. All units found to be in operational condition with no immediate service needs identified. Documented equipment condition through photographic records for maintenance file.
Completed full A/C retrofit installation including new Lennox outdoor condensing unit positioned on concrete pad with proper clearances and a new evaporator coil integrated with existing furnace system. Installed all refrigerant line sets, electrical connections, condensate drain piping with proper trap configuration using white PVC, and reflective metallic supply ductwork with appropriate sealing and insulation to ensure efficient airflow and system performance.
Installed structural wall bracing and metal mounting brackets to support air handler units in new construction space. Secured L-bracket supports to wall studs with appropriate fasteners to ensure proper load-bearing capacity for equipment installation.
Completed full HVAC system replacement in residential basement, installing new high-efficiency furnace and air conditioning system. Configured all ductwork connections, PVC venting, condensate drainage lines, refrigerant lines, and electrical controls to manufacturer specifications. System tested and verified operational, with all components properly mounted and secured on concrete pad in utility area.
Completed scheduled commercial cooling maintenance on rooftop HVAC unit. Performed system inspection, verified operational parameters using digital testing equipment, and documented unit condition with refrigerant line connections intact and properly insulated. All components found operating within normal specifications with condenser fan assembly and electrical controls functioning properly.
Completed spring maintenance on commercial HVAC unit. Performed comprehensive system inspection and testing of electrical components using digital multimeter. Verified capacitor readings at 35.14 MFD and measured voltage at 5.09 volts on system components. Inspected condenser coil fins, which were found to be clean and in good operational condition. All measurements within normal operating parameters. Unit operating properly upon completion of preventive maintenance service.
Completed Magic Pack chassis replacement on through-wall air conditioning unit. Removed existing chassis from wall sleeve, installed new replacement chassis, and verified proper fit and mounting within the existing opening. Unit tested successfully with secure installation confirmed.
Responded to service call for reported leak under kitchen sink. Upon arrival, inspected under-sink plumbing assembly and identified active leak at deteriorated metal elbow joint connection where it meets white PVC trap assembly. Observed water accumulation in bucket positioned beneath leak point, confirming ongoing drainage issue.
Examined trap configuration and noted significant age-related deterioration on metal components, including visible oxidation and corrosion at threaded connections. Assessed condition of white PVC pipes and connections, observing discoloration and staining around joint areas indicating prolonged moisture exposure. Inspected braided flexible supply lines and confirmed they remained intact with no visible damage.
Conducted additional inspection of basement plumbing infrastructure to trace potential related issues. Examined exposed piping runs including PVC drain lines and supply pipes throughout basement ceiling joists. Verified no additional leak points or c
Responded to service call for commercial air conditioning unit not activating. Found thermostat was set to Celsius temperature scale, preventing proper unit operation. Reconfigured thermostat settings to Fahrenheit and verified system activation and proper communication with HVAC equipment. Unit now cycling correctly and maintaining desired temperature setpoint.
Completed boiler retrofit involving the replacement of an existing Triangle Tube boiler unit. Installation included reconnection of copper supply lines, flexible metallic hoses, and integration with existing PVC drainage system, ensuring all plumbing connections were properly secured and tested for system functionality.
Completed maintenance agreement cooling service on two air conditioning systems, both over 10 years old. Performed comprehensive inspection and maintenance on both units, including filter evaluation. Documented heavily soiled air filters showing significant accumulation of dust, dirt, and debris with yellow-tan discoloration, indicating extended service period without replacement. Filters displayed restricted airflow capacity due to particulate buildup. Captured photographic documentation of filter conditions for maintenance records. Systems evaluated and serviced per maintenance agreement specifications.